Absorption cooling uses heat to move heat

Absorption cooling uses heat to move heat

By Phil Springer, Editor · Published · Prepper Stumper

Absorption cooling uses heat to move heat

Absorption cooling runs a refrigeration cycle with heat as its principal driving input. A conventional vapour-compression refrigerator uses a mechanical compressor to circulate refrigerant between different conditions. An absorption machine replaces that compressor's role with an absorber, a liquid-solution pump and a heated generator. The cycle can be driven by steam, hot water or recovered engine exhaust. The same broad family of technology includes small refrigerators and large chillers supplying cooling to buildings and industrial processes.

The refrigerant still evaporates to take in heat from the space or fluid being cooled. Its vapour then enters an absorber, where it dissolves in another liquid. A pump raises the pressure of that solution. In the generator, added heat separates refrigerant vapour from the absorbent. The refrigerant can then condense and return towards the evaporator, while the absorbent returns to take up more vapour. The apparatus moves energy through a repeating circuit of evaporation, absorption, separation and condensation.

The two substances have different roles. In many building chillers, water is the refrigerant and lithium bromide solution is the absorbent. For lower-temperature duties, ammonia can be the refrigerant and water the absorbent. Water therefore occupies opposite roles in the two combinations. The choice of pair changes the useful operating range. Absorption cooling is also distinct from adsorption cooling, where the sorbent is a solid, commonly silica gel, rather than a liquid solution.

Large absorption cooling installations can recover thermal energy that would otherwise leave a power-producing system as waste heat. Combined heat and power equipment may include reciprocating engines, microturbines or combustion turbines. Their exhaust or recovered hot water can supply a chiller. A documented metal-fabrication installation in Fitchburg, Massachusetts, coupled a 400-ton single-stage chiller with three 600-kilowatt reciprocating engines. Related applications include district energy plants, manufacturing facilities, cold-storage warehouses and buildings with sustained cooling demand.

The amount of cooling is often compared with the heat supplied through a coefficient of performance. This thermal ratio is different from the electrical performance measure for a motor-driven chiller. Single-effect and multiple-effect absorption machines also differ. Additional generator effects can reuse thermal energy within the system, but require higher-temperature heat. A 2014 Department of Energy review described typical thermal coefficients around 0.6–0.7 for single-effect systems, 1.1–1.3 for double-effect systems and 1.6–1.7 for triple-effect systems.

One historical branch involved Albert Einstein and Leo Szilard. Their United States patent 1,781,541 was granted on 11 November 1930, following a December 1927 application. The patent named Electrolux Servel Corporation as assignee. Its proposed refrigeration circuit used evaporation in the presence of another gas. The design referred explicitly to earlier work by Baltzar von Platen and Carl Munters, whose United States patent had been granted in 1928.

Einstein and Szilard's example used butane as refrigerant, ammonia as the accompanying gas and water as the absorbing liquid. Ammonia lowered butane's partial pressure in the evaporator, allowing the butane to evaporate. Elsewhere, water absorbed the ammonia, allowing the butane to condense. Heating released ammonia from solution for reuse. The fluids had different functions from the ammonia-water pair used in other absorption equipment. Calling both systems absorption refrigerators does not make their internal cycles identical.

Their patent described a system operating at substantially uniform total pressure, apart from small differences associated with liquid columns and circulation. It included a heat-driven liquid lift and an exchange of heat between stronger and weaker solutions. This was a particular proposed arrangement within refrigeration engineering, rather than the origin of all heat-driven cooling. Its patent date, named inventors and fluid roles place it within an already developing field of absorption designs.

Research continued long after these early household concepts. A University of Maryland project funded by the Department of Energy ran from 2019 to 2022 and investigated a microemulsion absorbent. Its proposal combined a new working-fluid pair with an electrostatic desorber. The published objective was a single-effect prototype with a thermal coefficient of performance of 2.0. That number was a research target, not a reported result establishing that every absorption chiller could achieve it.

In absorption cooling, the absorption step releases heat into the condenser-water and cooling-tower loop. This additional rejection load means that a machine needs a larger cooling tower than a mechanical chiller of equal capacity. The usual thermal coefficient excludes energy consumed by the solution pump, fans and other auxiliaries. In one ammonia-water installation, two reciprocating generators rated at 415 kilowatts each supplied waste heat for 160 tons of refrigeration. The cooling served a cold room at a food-processing plant. Boiler efficiency was also omitted from calculations for the hot-water and steam-driven example machines.

The Question

What chiefly drives the generator in an absorption refrigeration cycle?

Show the answer

The Answer

A heat input separates refrigerant from the absorbent in the generator, driving the thermal cycle.